EASY DMX SO
Installation
Installation
Mounting the control unit
Mounting Dismounting
Wiring limitations
When planning the DMX link, the following considerations must be taken into ac-
count in addition to the information provided in corresponding DMX device instruction
sheets:
For outdoor installations, only use data cables designed for exterior use.
Typical DMX cable properties:
low capacitance
impedance: 85 to 150 ohms
electrically shielded
at least 1 twisted pair of conductors
minimum wire size: 0.25 mm² (AWG 24) for runs up to 300 meters
CAT 5 network cables designed for direct burial can be used, but it is recom-
mended to use conduits
DMX devices must be “daisy-chained” (DMX cable must be connected in one single
chain of DMX devices).
Max. 32 DMX devices per chain. See the separate instruction sheets of the DMX
devices for exceptions.
An optically isolated amplier or splitter must be used to:
amplify the DMX signal in environments with a high degree of electromagnetic
interfaces
extend a link beyond 300 meters
extend a link to include another 32 DMX devices maximum
branch the link into further single chains, each containing max. 32 DMX devices